Digital Twin of Distribution Power Transformer for Real-Time Monitoring of Medium Voltage From Low Voltage Measurements

机译:数字双孪生分配电力变压器,用于实时监测低电压测量的中电压

获取原文
获取原文并翻译 | 示例

摘要

Real-time monitoring of distribution systems has become necessary, due to the deregulation of electricity markets and the wide deployment of distributed energy resources. To monitor voltage and current at sub-cycle detail, requires, typically, major investment undertaking and disruptions to the operation of the grid. In this work, measurements of the low voltage (LV) side of distribution transformers (T/F) are used to calculate in real time the waveforms of their medium voltage (MV) sides, based on a mathematical model of said T/F. This model is, essentially, the digital twin of the MV side of the T/F. The method calculates T/F MV waveforms of voltage and current, and active and reactive power as accurately as an instrument T/F, captures all harmonics content, is unaffected by asymmetrical loading and identifies most system faults on the MV side of the T/F. The digital twin method enables monitoring of distribution T/F that avoids MV instrumentation, does not suffer in accuracy and may be readily deployable. Field data from an actual MV-LV T/F, agree with simulation results showcasing the efficacy of the digital twin method.
机译:由于电力市场放松管制和分布式能源广泛部署,对分配系统的实时监测已成为必要的。监测子周期细节的电压和电流,通常需要重大投资和对网格的运行中的扰乱。在这项工作中,基于所述T / F的数学模型,使用分布式变换器(T / F)的低压(LV)侧的测量来实时计算其中压(MV)侧的波形。该模型基本上是T / F的MV侧的数字双胞胎。该方法计算电压和电流的T / F MV波形,以及作为仪器T / F的主动和无功功率,捕获所有谐波内容,不受不对称加载的影响,并识别T / MV侧的大多数系统故障。 F。数字双床方法可以监控避免MV仪器的分布T / F,不忍受精度,并且可以易于部署。来自实际MV-LV T / F的现场数据,同意模拟结果展示了数字双胞胎方法的功效。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号