首页> 外文期刊>Instrumentation and Measurement, IEEE Transactions on >Traceability of Low-Power Voltage Transformer for Medium Voltage Application
【24h】

Traceability of Low-Power Voltage Transformer for Medium Voltage Application

机译:适用于中压应用的小功率电压互感器的可追溯性

获取原文
获取原文并翻译 | 示例
           

摘要

In this paper, the measuring and calibration techniques useful for ensuring the traceability of nonconventional voltage transformer (VT), used in ac power plant up to 52 kV, are described and discussed. In particular, a setup made by commercially available devices is presented and an in-depth accuracy analysis is performed by considering all the uncertainty sources located in the measurement chain. The obtained results prove that it can be used for the calibration of 0.5 accuracy class low-power VTs. In addition, the sources that contribute more to the uncertainties on the ratio and phase errors are highlighted and suggestions on where to act to further improve the accuracy of the presented setup are given.
机译:在本文中,描述和讨论了用于确保非常规电压互感器(VT)的可追溯性的测量和校准技术,该电压高达520 kV的交流电站中使用。特别是,介绍了由可商购设备进行的设置,并通过考虑位于测量链中的所有不确定性源来进行深度精度分析。获得的结果证明,它可以用于0.5精度等级的低功率VT的校准。此外,重点介绍了对比例和相位误差的不确定性有更大贡献的来源,并提出了在何处采取行动以进一步提高所提出设置的准确性的建议。