首页> 外文期刊>IEEE Transactions on Instrumentation and Measurement >Measurements and Correction of No-Load Losses of Power Transformers
【24h】

Measurements and Correction of No-Load Losses of Power Transformers

机译:电力变压器空载损耗的测量与校正

获取原文
获取原文并翻译 | 示例
           

摘要

This paper investigates the practice of correcting the results of no-load loss measurements of power transformers for the effect of distorted supply voltage waveform. A three-phase 700-MVA power transformer is tested twice: first with its low-voltage windings connected line-to-neutral, with nearly sinusoidal test voltage conditions, and then for the second test with its windings connected line-to-line with more distorted voltage waveforms. The test data obtained during the measurement was reproduced at the National Research Council (NRC) Laboratory to demonstrate the limits of the application of the loss correction formula currently used.
机译:本文研究了针对电源电压波形失真对功率变压器的空载损耗测量结果进行校正的实践。三相700-MVA电力变压器经过两次测试:首先将低压绕组线对中连接,测试电压条件接近正弦波,然后进行第二次测试,将绕组线与中性点连接。更多失真的电压波形。测量期间获得的测试数据在国家研究委员会(NRC)实验室中进行了复制,以证明当前使用的损耗校正公式的应用范围。