首页> 外文期刊>IEEE Transactions on Instrumentation and Measurement >No-load loss measurements of power transformers under distorted supply voltage waveform conditions
【24h】

No-load loss measurements of power transformers under distorted supply voltage waveform conditions

机译:电源电压波形失真的情况下电力变压器的空载损耗测量

获取原文
获取原文并翻译 | 示例

摘要

This paper describes the problem of correcting the results of no-load loss measurements of power transformers for the effect of distorted supply voltage waveform on the magnetic flux in the core and hence on both the hysteresis and eddy current loss components of core losses. Test data obtained during the no-load loss measurements of a three phase 675-MVA power transformer was reproduced at the National Research Council of Canada laboratory to demonstrate the instrumentation requirements to ensure a proper application of the correction formula.
机译:本文描述了由于电源电压波形失真对铁心中的磁通量以及因此对铁心损耗的磁滞和涡流损耗分量的影响而对电力变压器的空载损耗测量结果进行校正的问题。加拿大国家研究委员会实验室复制了三相675-MVA电力变压器的空载损耗测量期间获得的测试数据,以证明仪器要求可确保正确应用校正公式。