摘要

The applications of ventilated beam systems in the hot and humid climate are limited. The main reason is the high risk of condensation. A case-study measurement was conducted in a typical office building in Singapore to investigate the feasibility of a ventilated beam system in the Tropics. The results show that the condensation in the beam system is possible to prevent and to reach dry cooling if infiltration is minimized, supply airflow rate is sufficient to extract humidity of people and tuning of the automation system has conducted probably.
机译:通风梁系统在炎热和潮湿的气候中的应用受到限制。主要原因是冷凝的高风险。在新加坡的一幢典型办公楼中进行了案例研究测量,以研究在热带地区使用通风横梁系统的可行性。结果表明,如果将渗透率降至最低,则束流系统中的凝结有可能防止并达到干冷,供气流速足以抽出人员的湿度,并且可能已对自动化系统进行了调整。