首页> 外文会议>International Symposium on High-voltage engineering >Relative risks of end arm discharges on stator bars
【24h】

Relative risks of end arm discharges on stator bars

机译:终端臂放电对定子杆的相对风险

获取原文

摘要

Long term aging tests of stator bar end arms were carried out over two years. Six specimens affected by one of three types of defects were studied. The defects were corona activity around the junction of the armor and the end arm stress gradingsystem, surface tracking and bar-to-bar discharges. All the specimens were submitted to an aging voltage of 20 kV a.c. (2.5*U{sub}0). Phase resolved partial discharge (PRPD) and spectral analyses were performed periodically, to characterize each type ofactivity. After more than two years of aging, we noted that some types of activities were very sporadic, while others were more permanent. Three failures occurred up to now, two of them after less than 240 days of aging on specimens with corona activityat the junction. The third failure occurred on a specimen affected by bar-to-bar discharges after 680 days. Despite the fact that all failures occurred in the straight portion of the bars, we think that the corona activity was, at least partially,involved in the failure mechanism on each setup.
机译:定子杆末端臂的长期老化试验在两年内进行。研究了受三种类型缺陷中的一种影响的六种样本。缺陷是铠装的交界处的电晕活动和端部臂应力分级系统,表面跟踪和条形杆放电。将所有标本提交到20 kV A.C的老化电压。 (2.5 * u {sub} 0)。相间分辨的局部放电(PRPD)和谱分析定期进行,以表征每种类型的性能。经过两年多的衰老后,我们指出的是一些类型的活动非常零星,而其他活动则更加永久。目前已经发生了三次故障,其中两种在患有电晕活动的标本上少于240天后的老化。在680天后受酒吧到酒吧放电影响的标本发生第三失败。尽管所有故障发生在条形条的直线中,但我们认为电晕活动至少部分地参与每个设置的故障机制。