首页> 外文期刊>IEEE Transactions on Power Systems >Analytically Validated SSCI Assessment Technique for Wind Parks in Series Compensated Grids
【24h】

Analytically Validated SSCI Assessment Technique for Wind Parks in Series Compensated Grids

机译:串联补偿网格中的风蚀分析验证的SSCI评估技术

获取原文
获取原文并翻译 | 示例

摘要

This work highlights limitations in existing screening approaches to assess low-frequency interactions during interconnection studies of grid-connected inverters (GCIs), such as wind power plants. It then proposes a new screening methodology capable of addressing these limitations for realistic representations of power system components and GCIs. It demonstrates that the asymmetric input admittance characteristics of GCIs, whose consideration is required for proper stability assessment, can be accurately extracted with the proposed adequate scanning method implemented in an electromagnetic transient (EMT) software package. This is verified through rigorous validation against analytical formulations developed for field validated type-III and type-IV wind turbine models. It shows that the technique is capable of correctly assessing stability in all presented cases. All results are validated against detailed EMT simulations.
机译:这项工作突出了现有筛选方法的限制,以评估网格连接逆变器(GCIS)的互连研究期间评估低频相互作用,例如风力发电厂。然后,提出了一种新的筛选方法,能够解决电力系统组件和GCI的现实表示的这些限制。它表明GCIS的非对称输入进入特性,其考虑是适当的稳定性评估,可以用电磁瞬态(EMT)软件包中的提出的适当扫描方法精确提取。这通过对现场验证的III和IV型风力涡轮机模型开发的分析配方进行严格验证来验证。结果表明,该技术能够在所有呈现的情况下正确评估稳定性。所有结果都针对详细的EMT模拟验证。