Low-impedance faults are difficult to contain from the point of view of cover retention and tank rupture in pole-type distribution transformers. When evaluating a transformer's containment capabilities, one needs to consider two aspects: the overpressure caused by an arc of given parameters and the pressure withstand of the tank. This paper presents two methods to calculate overpressures as a function of the arc and all of the relevant geometrical parameters: tank diameter, air-space height, and the depth of the arc below the oil. Both methods have been validated with experiments. Results of tests to determine the pressure withstand of typical tanks are presented. It was found that an average value of the overpressure withstand capability is approximately 100 kPa. For a given tank geometry and fault parameters, a current-limiting fuse would be required if the methods proposed here predict an overpressure of more than 100 kPa.
机译:从极型配电变压器的罩盖保持和储罐破裂的观点来看,低阻抗故障很难得到遏制。在评估变压器的密封能力时,需要考虑两个方面:由给定参数的电弧引起的过压和储罐的耐压性。本文提出了两种方法来计算作为电弧和所有相关几何参数的函数的超压:油箱直径,气隙高度和油底下的电弧深度。两种方法均已通过实验验证。给出确定典型储罐耐压性的测试结果。发现超压承受能力的平均值约为100kPa。对于给定的储罐几何形状和故障参数,如果此处提出的方法预测过压超过100 kPa,则将需要限流熔断器。