When an electric arc is generated in transformer oil, a strong overpressure may rapidly develop in the tank, especially for low-impedance faults. This paper presents the test method and results obtained in a project aimed at assessing the human and environmental risks associated with this type of fault. Limit energy and pressure values were defined in terms of different safety levels. The best method of limiting the energy and pressure at a safety level in the transformer tank during internal faults of greater than 1.7 kA is to protect the transformer with a current limiting fuse. Other ways to increase the mechanical withstand of transformer tanks under such faults are also discussed.
机译:当变压器油中产生电弧时,油箱中可能会迅速形成强大的过压,特别是对于低阻抗故障。本文介绍了旨在评估与此类故障相关的人员和环境风险的项目中的测试方法和结果。极限能量和压力值是根据不同的安全级别定义的。在内部故障大于1.7 kA时,将能量和压力限制在变压器油箱中安全水平的最佳方法是使用限流熔断器保护变压器。还讨论了在此类故障下增加变压器箱的机械承受力的其他方法。