In this paper, a new concept for analyzing the dielectric severity supported along transformer windings when a transformer is submitted to a nonstandardized transient voltage waveform induced by switching operation of a vacuum circuit breaker (VCB) is examined. There are two new factors considered for evaluating the severity supported by the insulation windings in factory and in service. One factor is based on the methodology suggested by the authors called time-domain severity factor and another one is the frequency-domain severity factor. Both methodologies are here applied to two case studies in order to show and compare their capabilities and sensibilities to detect the risk of dielectric failures. The analyzed case studies, performed as practical applications, consist of: 1) a power transformer submitted to damped oscillatory waves at the resonant frequency and 2) a power system consisting of a power transformer connected to a VCB.
机译:在本文中,研究了一种新概念,用于分析当变压器承受由真空断路器(VCB)的开关操作引起的非标准化瞬态电压波形时沿变压器绕组支撑的介电强度。在评估工厂和服务中绝缘绕组支持的严重性时,考虑了两个新因素。一个因素是基于作者提出的称为时域严重性因子的方法,另一种是频域严重性因子。两种方法在此都应用于两个案例研究,以显示和比较其检测电介质故障风险的能力和敏感性。在实际应用中执行的分析案例研究包括:1)经受共振频率衰减振荡波的电力变压器,以及2)由连接到VCB的电力变压器组成的电力系统。