Measurement of the Dielectric Recovery Strength and Reignition of AC Contactors

机译:交流接触器的介电恢复强度和复燃的测量

获取原文
获取原文并翻译 | 示例

摘要

In order to understand the recovery characteristics of AC contactors and improve their performance, experimental measurements were used to investigate the arcing gap recovery process including dielectric recovery strength and reignition, to a pair of splitter plate together and four kinds of arc chamber of AC contactors. A special circuit was designed to perform the work. It demonstrates that under lower current, the dielectric recovery strengths of all kinds of arc chambers in the paper have no significant difference. However, with the increase of current, the difference of dielectric recovery strengths of them is much clear. The reignition characteristics of a pair of splitter plate and arc chambers are similar. With different configurations of arc chambers and prospective currents, the forms of post current zero reignition are distinct.
机译:为了了解交流接触器的恢复特性并提高其性能,采用实验方法研究了电弧间隙恢复过程,包括介电恢复强度和复燃,对一对隔板和交流接触器的四种灭弧室。设计了专用电路来执行这项工作。结果表明,在较低电流下,纸中各种电弧室的介电恢复强度无明显差异。但是,随着电流的增加,它们的介电恢复强度的差异就很明显了。一对隔板和电弧室的点火特性相似。在电弧室和预期电流的配置不同的情况下,后电流零复燃的形式是不同的。