首页> 外文会议>International Conference on Electrical Contacts >Measurement of the Dielectric Recovery Strength and Analysis of Reignition Process in Deion Plate Chambers of the AC Contactor
【24h】

Measurement of the Dielectric Recovery Strength and Analysis of Reignition Process in Deion Plate Chambers of the AC Contactor

机译:AC接触器DEION板腔室介电恢复强度及分析分析

获取原文

摘要

The process of dielectric recovery in the period of current zero has a close relation with the electric life of AC contactors under AC-4 duty condition. In order to fast evaluate the arc quenching performance of chambers, the experimental system based on Rabus' Substitute Principle has been used to measure the dielectric recovery strength of deion plate quenching chambers with different configurations. In this paper, not only the dielectric recovery strength are measured, but also numerical analysis of electric and gas-flow field are carried out for the deion plates with different arrangements. Combining the results of measurements and calculations, the influences of different arrangements of deion plates on the process of reignition and the dielectric recovery have been analyzed for AC contactor.
机译:当前零期间的介电恢复过程与AC-4占空比下的AC接触器的电寿命具有密切的关系。 为了快速评估腔室的电弧淬火性能,基于Rabus替代原理的实验系统已经用于测量具有不同配置的Deion板淬火室的介电恢复强度。 在本文中,不仅测量了介电恢复强度,而且对具有不同布置的DEION板进行电气流场的数值分析。 结合测量结果和计算结果,对AC接触器的分析了对重新判断过程的不同布置和介电回收的影响。