Experimental investigation of the dielectric recovery strength between the separating contacts of vacuum circuit breakers

机译:真空断路器隔离触头之间介电恢复强度的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

An experimental investigation has been carried out to examine the dielectric recovery strength of two commercial vacuum circuit breakers rated 15 kV and 7.2 kV, respectively, using the substitute method of Rabus. The two breakers exhibited different characteristics when tested up to 45 kV; continuous repetitive breakdowns occurred with the 7.2 kV device but not with the 15 kV interrupter, reflecting the influence of different contact materials. Variability in the initial rate of rise of dielectric strength was observed for both breakers. Tests indicated that the dielectric characteristic of vacuum breakers may depend upon the repetition rate of the probing voltage. It is concluded that, when evaluating a breaker by this method for a particular application, the recovery voltage should follow as closely as possible the voltage to be expected in service.
机译:已经进行了实验研究,以使用Rabus的替代方法来检查两个分别额定为15 kV和7.2 kV的商用真空断路器的介电恢复强度。在测试最高45 kV时,两个断路器表现出不同的特性。 7.2 kV设备连续发生重复性击穿,而15 kV灭弧室则没有发生,这反映了不同接触材料的影响。两种断路器的介电强度的初始升高速率均存在差异。测试表明,真空断路器的介电特性可能取决于探测电压的重复率。结论是,当针对特定应用通过这种方法评估断路器时,恢复电压应尽可能接近预期使用中的电压。