For pt.II see IEEE Winter Meeting, New Orleans, LA, 1986. A novel method for analyzing the steady-state and transient currents in the stator, rotor, and damper windings of a large generator is discussed, and the application of the method to five classes of problems of practical importance is described. These are (1) internal phase-to-phase fault in a two-circuit machine; (2) 180 degrees out-of-phase synchronization; (3) three-phase short circuit at generator terminals; (4) clearing of a three-phase system fau and (5) unbalanced steady-state negative phase sequence load of 6%. The authors show the individual damper bar currents and energies or electric power loadings for these cases and, for one example, the time variations of stator and damper winding currents. The investigation was conducted on a standard two-pole generator that was designed for 60 Hz operation and has a rating of 700 MW.
机译:对于第二点,请参见IEEE Winter Meeting,洛杉矶,新奥尔良,1986年。讨论了一种分析大型发电机的定子,转子和阻尼绕组中的稳态和瞬态电流的新颖方法,以及该方法的应用描述了具有实际重要性的五类问题。这些是(1)两回路电机内部的相间故障; (2)180度异相同步; (3)发电机端子三相短路; (4)清除三相系统故障; (5)6%的不平衡稳态负相序负载。作者显示了在这些情况下的单个阻尼棒电流和能量或电功率负载,并举例说明了定子和阻尼器绕组电流的时间变化。该调查是针对设计用于60 Hz运行且额定功率为700 MW的标准两极发电机进行的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号