首页> 外文期刊>Przeglad Elektrotechniczny >Design of a Passive 48-Pulse AC-DC Converter for THD Stabilization at Light Load
【24h】

Design of a Passive 48-Pulse AC-DC Converter for THD Stabilization at Light Load

机译:用于轻负载的稳定稳定的无源48脉冲AC-DC转换器的设计

获取原文
获取原文并翻译 | 示例

摘要

In this paper a 48-pulse uncontrolled AC-DC converter is proposed to mitigate AC line current harmonics of the input side. The proposed rectifier uses conventional 24-pulse parallelly connected rectifier with addition of a passive current injection circuit named as special interphase reactor. The interphase reactor consists of two additional lower rated power diodes. The value of the found THD is 3.55% which satisfies the IEEE 519-1992 standard. Proposed converter also shows lower fluctuation of harmonics valued 1.40% with respect to full load ensuring stable operation at light load. Designed multipulse converter scheme is also simple in construction and requires less number of electronic devices compared to conventional 48-pulse AC-DC converter. This article also explains the simulation and THD performance of the proposed AC-DC converter with proper figures.
机译:在本文中,提出了48脉冲不受控制的AC-DC转换器,以减轻输入侧的AC线电流谐波。所提出的整流器使用传统的24脉冲并行连接整流器,并添加了被动电流喷射电路,该电流注入电路命名为特殊的相互作用。间反应器由两个额外的较低额定功率二极管组成。发现THD的值为3.55%,满足IEEE 519-1992标准。所提出的转换器还表现出在充分负荷下确保在轻负载下稳定运行的满负荷的次要谐波波动。与传统的48脉冲AC-DC转换器相比,设计的多集体转换器方案也简单,需要少量的电子设备。本文还解释了所提出的AC-DC转换器的模拟和THD性能,具有适当的图。