Power quality improvements in 25kV 50 Hz railway substation based on chopper controlled impedances

机译:基于斩波器控制阻抗的25kV 50 Hz铁路变电站的电能质量改善

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Ce travail est le résultat d'une collaboration entre le laboratoire LAPLACE, la "Seconda Università degli Studi di Napoli" (SUN) et la Société National des Chemins de fer Français SNCF. Le sujet de recherche concerne l'utilisation de dispositifs électroniques de puissance dans les sous stations ferroviaires 25kV/50Hz afin d’améliorer la qualité de l'énergie électrique. Dans le transport ferroviaire, le système d'électrification monophasé 25kV/50Hz est largement diffusé en particulier pour les lignes ferroviaires à grande vitesse. Bien qu'aujourd'hui les systèmes d’alimentation en courant continu soient encore largement utilisés, l'adoption du courant alternatif monophasé offre des avantages économiques pour les infrastructures d'environ 30% en termes d'investissement, d'exploitation et d'entretien. Initialement, compte tenu de la simplicité du circuit, il n'y avait aucune nécessité d'intégrer de l'électronique de puissance dans les sous stations. Toutefois, au cours de la décennie passée, l'intérêt pour ces équipements est apparu car ils peuvent apporter une solution d'optimisation du réseau lorsque le trafic augmente ou lorsqu’une nouvelle sous station est envisagée. Deux principaux types de dispositifs sont installés aujourd'hui sur le réseau ferré français : les compensateurs de puissance réactive et les compensateurs de déséquilibre de tension. Cette thèse présente de nouvelles topologies de compensateurs basées sur le concept d’impédances contrôlées par gradateur MLI. Comparées aux solutions existantes, ces topologies ont des caractéristiques particulièrement intéressantes en termes de pertes dans les semi-conducteurs et de volume des composants réactifs. Le manuscrit contient trois parties principales: La première partie présente le principe de l’électrification en 25kV/50Hz et souligne l’intérêt d’installer des moyens de compensation statique dans les sous stations. Après une description des solutions actuellement utilisées, le concept d’impédance contrôlée par gradateur MLI (CCI : Chopper Controlled Impedance ) est ensuite présenté. La deuxième partie du travail concerne l'utilisation du concept de CCI pour la compensation de puissance réactive. La sous-station SNCF de Revest est considérée comme cas d’étude. Celle-ci est équipée d'un transformateur monophasé de 60MVA dont le primaire est connecté à une ligne de transport 225kV. Deux topologies de compensateur de puissance réactive, basées sur des montages abaisseur ou élévateur de tension sont présentées. Le dimensionnement des gradateurs est effectué sur la base d'une campagne de mesures réalisée à la sous station. Des simulations numériques utilisant des formes d’ondes réelles de courant et de tension sont présentées. Des résultats expérimentaux effectués à la plateforme de test de la SNCF sur un prototype de 1,2MVAR permettent de valider le concept de CCI. La dernière partie du travail concerne le problème du déséquilibre de tension en amont de la sous station.Un circuit de Steinmetz « actif », toujours basée sur des gradateurs MLI, est présenté et étudié. La sous station SNCF d'Evron est alors considérée comme cas étude. Celle-ci comporte un transformateur de 32MVA et est connectée à une ligne de transmission 90kV. Les mesures effectuées sur le site permettent le dimensionnement du compensateur ainsi que l’utilisation des formes d'onde réelles de courant et de tension dans les simulations numériques. Une comparaison avec des solutions classiques basées sur des onduleurs 2 niveaux et 3 niveaux souligne les avantages de la solution proposée. Ainsi, les résultats des calculs et des simulations montrent que l'énergie stockée dans les éléments réactifs est réduite d’un facteur six et que les pertes dans les semi-conducteurs sont réduites de 40%. Des résultats expérimentaux obtenus sur une maquette de 1.5 kVA permettent de valider le principe du circuit de Steinmetz actif. ABSTRACT : This work is the result of collaboration between the LAPLACE laboratory, the “Seconda Università degli Studi di Napoli” (SUN) and the French national railways operator SNCF. The research topic treated herein concerns the use of power electronic devices in 25kV/50Hz railways substations to achieve power quality improvements. In railway transportation, single-phase 25kV-50Hz electrification system is widely diffused especially for high-speed railway applications. Although electrified DC systems are still widely applied, the adoption of AC single-phase system offers economical advantages for the infrastructures of about 30% in terms of investment, exploitation and maintenance.In early ages, due to its very simple diagram, there was no necessity to integrate power electronics in substations. However, for the last decade, the interest in power electronic equipments raised since they can provide the solution for network optimization when traffic increases or when a difficulty is foreseen for a substation implementation. Two types of devices are implemented today on the French Railway Network: Reactive Power compensators and Voltage Unbalance compensators.This thesis presents an investigation into new topologies based on the concept of “Chopper Controlled Impedances”(CCI). Compared to existing solutions, the new topologies show interesting features in terms of semi-conductor losses reduction and volume of reactive components. The manuscript is developed through three main parts: Firstly, the French railways system is introduced and the interest in installing power electronic compensators in substations is highlighted. After a brief description of currently used solutions, the CCI concept is presented: the use of Pulse Width Modulated AC Choppers allows achieving structures which behave as variable impedances. In the second part, the use of CCI structures in reactive power compensation is investigated. The SNCF substation of Revest is under study. It is equipped by a 60MVA single phase transformer with the primary side connected to a 225kV transmission line. Based on the step-down or step-up functioning mode of CCIs, two topologies of reactive power compensator are presented. The converter design is developed on the base of a measurement campaign carried out at the substation. Numerical simulations using real current and voltage waveforms are presented. Finally, experimental results carried out at the SNCF test platform on a 1.2MVAR prototype are shown. In the last part, the problem of voltage unbalance is treated. Using the concept of CCI, the feasibility of an active Steinmetz circuit based on AC choppers is explored. As a case study, the substation of Evron is considered. It is a 32MVA substation connected to a 90kV transmission line. Measurements carried out on the substation site allow the compensator design and the possibility to consider real waveforms for current and voltage in numerical simulations. A comparison with classical solution based on two levels VSI and three levels NPC-VSI highlights the advantages of the proposed solution. Calculation and simulation results show that the stored energy in reactive elements is reduced by a factor six whereas the semiconductor losses are 40% lower. Experimental results obtained on a scaled demonstrator (1.5 kVA) validate the principle of the active Steinmetz circuit.
机译:这项工作是LAPLACE实验室,“那不勒斯的塞康达大学”(SUN)和法国国家化学工业协会(SNCF)之间合作的结果。该研究主题涉及在25kV / 50Hz铁路变电站中使用电子电力设备,以提高电能质量。在铁路运输中,广泛使用25kV / 50Hz单相电气化系统,特别是在高速铁路上。尽管今天仍广泛使用直流电源系统,但单相交流电的采用为基础设施带来了约30%的经济优势,包括投资,运营和运营成本。面试最初,由于电路简单,因此无需在变电站中集成电力电子设备。但是,在过去的十年中,人们对这种设备产生了兴趣,因为它可以为流量增加或计划新的变电站提供优化网络的解决方案。今天,法国铁路网络上已安装了两种主要类型的设备:无功功率补偿器和电压不平衡补偿器。本文提出了基于PWM调光器控制阻抗概念的新型补偿器拓扑。与现有解决方案相比,这些拓扑在半导体损耗和电抗组件的体积方面具有特别有趣的特性。该手稿包含三个主要部分:第一部分介绍了25kV / 50Hz的电气化原理,并强调了在变电站中安装静态补偿装置的兴趣。在描述了当前使用的解决方案之后,然后介绍了由调光器MLI控制的阻抗(CCI:斩波器控制阻抗)的概念。工作的第二部分涉及将CCI概念用于无功功率补偿。 Revest SNCF变电站被视为案例研究。它配备有60MVA单相变压器,其初级绕组连接到225kV输电线路。提出了基于升压或升压安排的两种无功功率补偿器拓扑。调光器的尺寸取决于变电站的测量工作。提出了使用实际电流和电压波形的数值模拟。在SNCF测试平台上对1.2MVAR原型进行的实验结果可以验证CCI的概念。工作的最后一部分涉及变电站上游的电压不平衡问题,提出并研究了始终基于PWM调光器的“有源” Steinmetz电路。然后将埃夫隆的SNCF变电站视为案例研究。这包括一个32MVA变压器,并连接到90kV传输线。在现场进行的测量允许补偿器的尺寸确定以及在数字仿真中使用实际电流和电压波形。与基于2级和3级逆变器的常规解决方案的比较突出了所提出解决方案的优势。因此,计算和模拟的结果表明,存储在电抗元件中的能量减少了六倍,并且半导体中的损耗减少了40%。在1.5 kVA模型上获得的实验结果可以验证有源Steinmetz电路的原理。摘要:这项工作是LAPLACE实验室,“那不勒斯塞康达大学”和法国国家铁路运营商SNCF合作的结果。本文涉及的研究主题涉及在25kV / 50Hz铁路变电站中使用电力电子设备以实现电能质量的改善。在铁路运输中,特别是在高速铁路应用中,单相25kV-50Hz电气化系统得到广泛推广。尽管电气化直流系统仍得到广泛应用,但交流单相系统的采用为基础设施在投资,开发和维护方面提供了约30%的经济优势。在早期,由于其非常简单的示意图,因此没有在变电站中集成电力电子设备的必要性。然而,过去十年引起了人们对电力电子设备的兴趣,因为它们可以在流量增加或变电站实施遇到困难时为网络优化提供解决方案。今天,法国铁路网络上已经实现了两种类型的设备:无功功率补偿器和电压不平衡补偿器。本文对基于“斩波器控制阻抗”(CCI)概念的新拓扑进行了研究。与现有解决方案相比,新拓扑在减少半导体损耗和减少无功组件的数量方面显示出有趣的功能。该手稿分为三个主要部分:首先,介绍了法国铁路系统,并强调了在变电站中安装电力电子补偿器的兴趣。在简要介绍了当前使用的解决方案之后,提出了CCI概念:使用脉宽调制交流斩波器可以实现表现为可变阻抗的结构。在第二部分中,研究了CCI结构在无功补偿中的使用。 Revest的SNCF变电站正在研究中。它配备有60MVA单相变压器,其初级侧连接到225kV输电线路。基于CCI的降压或升压功能模式,提出了两种无功补偿器的拓扑结构。变流器设计是基于变电站进行的测量活动而开发的。提出了使用实际电流和电压波形的数值模拟。最后,显示了在SNCF测试平台上针对1.2MVAR原型进行的实验结果。最后一部分,解决了电压不平衡的问题。使用CCI的概念,探讨了基于交流斩波器的有源Steinmetz电路的可行性。作为案例研究,考虑了埃夫隆变电站。它是连接到90kV输电线路的32MVA变电站。在变电站现场进行的测量允许进行补偿器设计,并有可能在数值模拟中考虑电流和电压的实际波形。与基于两个级别的VSI和三个级别的NPC-VSI的经典解决方案的比较突出了所提出解决方案的优势。计算和仿真结果表明,电抗元件中存储的能量减少了六分之一,而半导体损耗则降低了40%。在比例演示器(1.5 kVA)上获得的实验结果验证了有源Steinmetz电路的原理。

著录项

  • 作者

    Raimondo Giuliano;

  • 作者单位
  • 年度 2012
  • 总页数
  • 原文格式 PDF
  • 正文语种
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号