首页> 外文OA文献 >Voraussetzungen des Überstromzeitschutzes in wechselrichterbasierten gewollten Inselnetzen unter Berücksichtigung von Strombegrenzung und transienter Stabilität
【2h】

Voraussetzungen des Überstromzeitschutzes in wechselrichterbasierten gewollten Inselnetzen unter Berücksichtigung von Strombegrenzung und transienter Stabilität

机译:考虑到电流限制和瞬态稳定性,在基于逆变器的故意独立电网中进行过电流保护的前提条件

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Intentional islanding of electrical distribution systems raises potentials for customer backup power supply in future energy systems. An uncertain amount of additional expenses is needed to ensure an adequate and reliable protection system for the islanded mode of operation. Nowadays, customer installations are mainly equipped with low-cost overcurrent protection devices. Their reliable fault tripping is assumed but is not verified in intentionally islanded grids built by multiple inverter coupled distributed energy resources. It is unknown, whether critical influences and requirements need to be taken into consideration in addition to a sufficient dimensioning of the sources. Potentially influencing factors are investigated by means of time domain simulations of an islanded low voltage distribution system containing two grid building inverters. One and three phased faults are investigated in main and final circuits of customer installations. A sensitivity analysis varies up to 32 factors simultaneously from the areas grid structure and parameters, dimensioning of inverters, inverter neutral current injection capability as well as structure and parameters of LCL-filters, control circuits, current limiting mechanisms and anti-windup. For the first time, these variation studies consider an increasing degree of inhomogeneity of structure and parameter settings and exploit a significant bandwidth of values per setting. A rule based procedure is created as a precondition for parameterizing the overall model and the control circuits. Adequate variants of inverter current reference limiting mechanisms are identified by means of a developed test procedure. For the first time, according mechanisms are systematically derived for grid building inverters with neutral current injection capability.Reliable tripping of overcurrent protection devices is achievable for single wire final circuits with tripping times lower than 400ms, when a successful fault ride through can be ensured for an adequate quantity of grid building inverters. The required installed rated inverter currents are in the range from 0.92 to 1.18 times the overcurrent protection device’s tripping current. Influencing factors are the current limiting mechanisms used, the type of overcurrent protection installed and the inhomogeneity of inverter control structures present.Faults in main circuits experience a critical influence by a loss of transient stability during the fault (desynchronization) due to the resulting longer prospective tripping times. A reliable protection tripping is then impeded by the resulting gradual or cyclic reduction of the total fault current available. In case of three phased faults, the development over time can be estimated by a small number of factors. For one phased faults, an increase of the number of desynchronizing cases is observed with increasing degree of structural inhomogeneity. Dependable tripping is potentially achievable, when mechanisms for reliably avoiding desynchronization are utilized. In that case, an adequate number of inverters must ride through the fault.A fault ride through capability of the grid building inverters requires those to supply and tolerate phase voltages in the range of zero to 1.08*sqrt(3) p.u. and line-line voltages up to 1.175 p.u. Partial loading and reverse power capabilities are required from the inverter coupled distributed energy resources. Cyclic overloading of single phases or complete inverters can occur especially in case of a desynchronization.
机译:配电系统的有意孤岛化为将来的能源系统中的客户备用电源提供了潜力。要确保对孤岛式操作模式有足够而可靠的保护系统,就需要不确定的额外费用。如今,客户设备主要配备了低成本的过流保护装置。假设它们具有可靠的故障跳闸功能,但在由多个逆变器耦合的分布式能源构建的有意孤岛电网中未得到验证。未知的是,除了适当确定源的尺寸外,是否还需要考虑关键影响和要求。通过包含两个并网逆变器的孤岛低压配电系统的时域仿真,研究了潜在的影响因素。在客户安装的主电路和最终电路中调查一相和三相故障。灵敏度分析最多可同时更改32个因素,这些因素包括区域网格结构和参数,逆变器的尺寸,逆变器中性点电流注入能力以及LCL滤波器的结构和参数,控制电路,限流机制和抗饱和。这些变化研究首次考虑到结构和参数设置的不均匀程度不断提高,并在每个设置中使用了大量的值带宽。创建基于规则的过程作为参数化总体模型和控制电路的前提。借助于开发的测试程序,可以识别出逆变器电流参考限制机制的适当变体。首次有系统地推导具有中性电流注入能力的并网逆变器的相应机制。当能够确保成功穿越故障时,对于跳闸时间小于400ms的单线最终电路,可以实现可靠的过电流保护装置跳闸。足够数量的并网逆变器。所需的已安装逆变器额定电流为过流保护设备的跳闸电流的0.92至1.18倍。影响因素是所使用的电流限制机制,安装的过电流保护的类型以及逆变器控制结构的不均匀性。主回路中的故障会因故障(失步)期间瞬态稳定性的损失而受到严重影响,这是由于预期寿命更长跳闸时间。然后,由于总的可用故障电流逐渐减小或周期性减小,从而阻碍了可靠的保护跳闸。在三相故障的情况下,可以通过少量因素来估算随时间的发展。对于一相故障,随着结构不均匀程度的增加,观察到失步情况的数量增加。当使用可靠地避免失步的机制时,有可能实现可靠的跳闸。在这种情况下,必须有足够数量的逆变器通过故障。电网建设型逆变器的故障通过能力需要那些提供并容忍相电压范围为零至1.08 * sqrt(3)p.u的逆变器。以及最高1.175 p.u.的线路电压逆变器耦合的分布式能源需要部分负载和反向功率功能。单相或整个逆变器的循环过载可能会发生,特别是在失步情况下。

著录项

  • 作者

    Wippenbeck Tilman;

  • 作者单位
  • 年度 2017
  • 总页数
  • 原文格式 PDF
  • 正文语种 ger
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号