首页> 美国政府科技报告 >Effect of Condensate Inundation on Steam Condensation Heat Transfer in a Tube Bundle
【24h】

Effect of Condensate Inundation on Steam Condensation Heat Transfer in a Tube Bundle

机译:凝结水淹对管束蒸汽凝结传热的影响

获取原文

摘要

Steam-condensation heat-transfer measurements were made using a 5-tube in-line test condenser with an additional perforated tube to simulate up to 30 active tubes. Results were obtained for smooth tubes wire-wrapped tubes and dropwise-coated tubes. The average outside heat-transfer coefficient for 30 smooth tubes was 0.64 times the Nusselt coefficient fo the first tube. A total of eight wire-diameter and wire-pitch combinations were tested: 1.6-mm-diameter wire wrapped at 16 mm, 7.6 mm and 4 mm wire pitches, 1.0-mm-diameter wire wrapped at 8 mm, 4 mm and 2 mm wire pitches, and 0.5-mm-diameter wire wrapped at 4 and 2 mm wire pitches. The best bundle performance was obtained when the tubewere wrapped with 1.0-mm-diameter wire at a wire pitch of 4 mm. This combination resulted in an average outside heat-transfer coefficient for 30 tubes that was 1.15 times the value computed for the first time using the Nusselt theory. The average outside heat-transfer coefficient for 30 dropwise-coated tubes was 1.1 times the value of the heat-transfer coefficient for the first tube in the tube bundle. Using either wire-wrapped tubes or dropwise-coated tubes, it is possible to significantly reduce the condenser surface area and overall size.