首页> 美国政府科技报告 >Flow and Temperature Distribution in a Naturally Stratified Thermal Storage Tank
【24h】

Flow and Temperature Distribution in a Naturally Stratified Thermal Storage Tank

机译:自然分层蓄热罐内的流量和温度分布

获取原文

摘要

Thermal energy storage for building and process cooling is employed in twoprincipal forms: sensible and latent. Each form has its advantages and disadvantages. Currently, water is the most frequently used storage medium for cooling, with the solid/liquid phase change being used for latent storage and chilled liquid water used for sensible storage. This report deals exclusively with sensible storage in water. Researchers studied the effects of mixing on the creation and maintenance of a thermocline during the charging of a thermal storage tank for cooling and the effects of momentum of inlet fluid and buoyancy due to temperature differences on the creation and maintenance of thermoclines. From the design point of view, the inlet parameters and their ranges for optimal performance of a stratified thermal storage tank have been more clearly delineated. The upper limit of the range of the Reynolds number for optimal stratified chilled water storage tank performance appears to be between 400 and 600. The upper limit of the densimetric Froude number range was determined in a previous study, and is about 2. Sensible storage, Thermal storage tank.