首页> 外文期刊>International Journal of Refrigeration >Approaching the performance limit for economized cycles using simplified cycles
【24h】

Approaching the performance limit for economized cycles using simplified cycles

机译:使用简化周期接近经济周期的性能极限

获取原文
获取原文并翻译 | 示例
           

摘要

Modifications such as economization aim to improve the efficiency of vapor compression equipment by cooling the refrigerant during the compression process. A previous study (Mathison et al., 2010) explored the theoretical limit to cycle performance with economizing, which was defined as the performance when a saturated vapor state was maintained in the compressor by continuously injecting a two-phase mixture. However, achieving continuous injection and controlling the quality of the injected refrigerant poses a substantial challenge. Therefore, the current paper investigates the ability of an economized cycle with saturated vapor injection through a finite number of ports to approach the limiting cycle performance. For an air-conditioner using R-410A with an evaporation temperature of 5℃ and a condensing temperature of 40℃, the model predicts that injecting saturated vapor through three ports will improve the COP by 12%, which is approximately 67% of the maximum benefit provided by economizing in the limiting case.
机译:节能等修改旨在通过在压缩过程中冷却制冷剂来提高蒸气压缩设备的效率。先前的研究(Mathison等,2010)探讨了节流循环性能的理论极限,即通过连续注入两相混合物在压缩机中保持饱和蒸汽状态时的性能。然而,实现连续喷射和控制喷射的制冷剂的质量提出了重大挑战。因此,当前的论文研究了通过有限数量的端口进行饱和蒸气注入的节能循环达到极限循环性能的能力。对于使用R-410A且蒸发温度为5℃且冷凝温度为40℃的空调,该模型预测,通过三个端口注入饱和蒸汽将使COP改善12%,大约是最高温度的67%通过在极限情况下节约而获得的收益。