首页> 外文期刊>Journal of Mechanical Science and Technology >Experimental study of the seawater fouling on a plate-frame heat exchanger for utilization of waste heat from powerplant
【24h】

Experimental study of the seawater fouling on a plate-frame heat exchanger for utilization of waste heat from powerplant

机译:电型换热器海水污垢的试验研究,从而利用供电者废热

获取原文
获取原文并翻译 | 示例
           

摘要

The overall heat transfer coefficient, pressure drop, and the fouling thermal resistance were compared between a clean and a seawater-exposed, fouled plate-frame heat exchanger. The fouled heat exchanger was utilized for heat recovery from the seawater-effluent for 3 months at a powerplant site. The performance tests were conducted at temperatures of 20 degrees C and 30 degrees C on the fouled-side, while the corresponding temperatures on the clean-side were 15 degrees C and 25 degrees C, respectively. Flow rate ranged from 20 to 40 l.min(-1) on the fouled-side and the clean-side of the heat exchanger. In the absence of fouling, the average U value was higher than that under the fouling condition by 21.3 %. The average thermal resistance ranged from 0.135 m(2).K.kW(-1) to 0.157 m(2).K.kW(-1). The pressure drop was less than 2 kPa with the change of temperature, but the pressure drop of the fouled-side increased by 400 % compared with that of the clean-side.
机译:在清洁和海水暴露的污垢的板框架热交换器之间比较了整体传热系数,压降和污垢热阻。 污垢的热交换器用于在动力空间在海水 - 流出物中热回收3个月。 在污垢侧的20摄氏度和30℃的温度下进行性能测试,而洁净侧的相应温度分别为15℃和25℃。 流速范围为20至40L.min(-1)在换侧和热交换器的清洁侧。 在没有污垢的情况下,平均值高于污垢条件下的u值率高21.3%。 平均热阻范围为0.135米(2).k.kw(-1)至0.157 m(2).k.kw(-1)。 随着温度的变化,压降小于2kPa,但与清洁侧相比,污垢侧的压降增加了400%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号