Reduction in MRSA environmental contamination with a portable HEPA-filtration unit.

机译:便携式HEPA过滤装置可减少MRSA环境污染。

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

There is renewed interest in the hospital environment as a potentially important factor for cross-infection with methicillin-resistant Staphylococcus aureus (MRSA) and other nosocomial pathogens. The aim of this study was to evaluate the effectiveness of a portable high-efficiency particulate air (HEPA)-filtration unit (IQAir Cleanroom H13, Incen AG, Goldach, Switzerland) at reducing MRSA environmental surface contamination within a clinical setting. The MRSA contamination rate on horizontal surfaces was assessed with agar settle plates in ward side-rooms of three patients who were heavy MRSA dispersers. Contamination rates were measured at different air filtration rates (60-235 m(3)/h) and compared with no air filtration using Poisson regression. Without air filtration, between 80% and 100% of settle plates were positive for MRSA, with the mean number of MRSA colony-forming units (cfu)/10-h exposure/plate ranging from 4.1 to 27.7. Air filtration at a rate of 140 m(3)/h (one patient) and 235 m(3)/h (two patients), resulted in a highly significant decrease in contamination rates compared with no air filtration (adjusted rate ratios 0.037, 0.099 and 0.248, respectively; P < 0.001 for each). A strong association was demonstrated between the rate of air filtration and the mean number of MRSA cfu/10-h exposure/plate (P for trend < 0.001). In conclusion, this portable HEPA-filtration unit can significantly reduce MRSA environmental contamination within patient isolation rooms, and this may prove to be a useful addition to existing MRSA infection control measures.
机译:对医院环境的重新关注已成为与耐甲氧西林金黄色葡萄球菌(MRSA)和其他医院病原体交叉感染的潜在重要因素。这项研究的目的是评估便携式高效颗粒空气(HEPA)过滤装置(IQAir Cleanroom H13,Incen AG,瑞士Goldach,瑞士)在减少临床环境中MRSA环境表面污染方面的有效性。在三个沉重的MRSA分散器患者的病房旁,用琼脂沉降板评估水平表面的MRSA污染率。在不同的空气过滤速率(60-235 m(3)/ h)下测量污染率,并与使用Poisson回归的无空气过滤进行比较。如果不进行空气过滤,则80%至100%的沉降板MRSA呈阳性,MRSA菌落形成单位(cfu)/ 10 h暴露/板的平均数为4.1至27.7。空气过滤的速度为140 m(3)/ h(一名患者)和235 m(3)/ h(两名患者),与不进行空气过滤相比,污染率显着降低(调整率比为0.037,分别为0.099和0.248;每个P <0.001)。空气过滤率和MRSA cfu / 10-h暴露/平板的平均数之间显示出很强的相关性(趋势<0.001的P)。总之,这种便携式HEPA过滤装置可大大减少患者隔离室内的MRSA环境污染,这可能是对现有MRSA感染控制措施的有用补充。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号