Assessment of the insulation serviceability of turbo-generator stators and of high-voltage bushings

机译:评估涡轮发电机定子和高压套管的绝缘使用寿命

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

The deterioration of the insulation in high-voltage turbo-generator stators can be followed by means of non-destructive tests. The relative merits of the available methods of testing stator insulation are given, but at present a single test will not reliably indicate the insulation condition. The detection of discharges with an electronic instrument most closely approaches this ideal and has the unique ability of indicating the existence of preferential deterioration near the line terminals of a high voltage stator. A dependable guide to the insulation condition can be obtained only from considering the results of several tests, employing both alternating and direct current. This allows the variation in the insulation of a turbo-generator stator undergoing normal usage to be determined. Departure from the normal variation indicates those machines that have suffered abnormal deterioration. The presence of deleterious discharges in high-voltage bushings at the time of manufacture has been ascertained with the E.R.A. discharge detector. The discharge magnitude is measured directly and has been related to the indirect methods normally used, such as loss angle and audible hiss. For synthetic-resin-bonded-paper bushings of 33????????132kV rating, some discharges are permissible near the working voltage. Discharges in oil-impregnated-paper bushings of 132, 220 and 330kV rating, however, are undesirable at the maximum working voltage. Recommendations are made of the permissible discharge magnitude for the two types of bushings.
机译:高压涡轮发电机定子的绝缘性能恶化可以通过无损检测来解决。给出了测试定子绝缘的可用方法的相对优点,但是目前仅进行一次测试将无法可靠地表明绝缘状况。用电子仪器检测放电最接近该理想,并且具有指示高压定子的线路端子附近存在优先劣化的独特能力。仅通过考虑使用交流电和直流电的几种测试的结果,才能获得可靠的绝缘条件指南。这允许确定经受正常使用的涡轮发电机定子的绝缘的变化。偏离正常变化表示那些机器已异常恶化。用E.R.A.已经确定了制造时高压套管中有害放电的存在。放电检测器。放电幅度是直接测量的,并且与通常使用的间接方法有关,例如损耗角和可听见的嘶嘶声。对于33〜132kV额定值的合成树脂粘合纸套管,在工作电压附近允许一些放电。然而,在最大工作电压下,不希望在132、220和330kV等级的浸油纸套管中放电。建议两种衬套的允许排放量。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号