首页> 外文期刊>Power Systems, IEEE Transactions on >One Markov Model for Spare Analysis of Distribution Power Transformers
【24h】

One Markov Model for Spare Analysis of Distribution Power Transformers

机译:一种用于配电变压器备件分析的马尔可夫模型

获取原文
获取原文并翻译 | 示例

摘要

This paper describes a probabilistic method for evaluating the number of spare units, regular spare transformers (RSTs), and mobile unit substations (MUSs) required for a group of similar distribution power transformers used at distribution stations in order to meet a pre-determined level of the group availability. The method uses a single Markov model for representing Class I and Class II failures of distribution transformers and a two-state model for representing the mobile unit substation (MUS). The two models are then convolved to obtain the required number of spare units. The proposed method is illustrated using a Hydro One sample of the distribution transformers and the results are compared with the previously published method.
机译:本文介绍了一种概率方法,用于评估配电站使用的一组相似配电变压器满足预定水平所需的备用单元,常规备用变压器(RST)和移动单元变电站(MUS)的数量组可用性。该方法使用单个马尔可夫模型来表示配电变压器的I类和II类故障,并使用两个状态模型来表示移动单元变电站(MUS)。然后将这两个模型进行卷积以获得所需数量的备用单元。使用Hydro One配电变压器样本对提出的方法进行了说明,并将结果与​​以前发布的方法进行了比较。