Closed loop testing of a joint VAr controller using a digital real-time simulator

机译:使用数字实时模拟器对联合VAr控制器进行闭环测试

获取原文
获取原文并翻译 | 示例

摘要

A joint VAr (volt-ampere reactive) controller is described which was designed for use at Manitoba Hydro's Dorsey converter station. The controller was tested in closed-loop mode using a fully digital real-time simulator. By performing a broad range of simulated system disturbances the controller's operation could be verified before its installation. The testing proved useful in verifying the controller concept, confirmed proper operation of the controller software, and allowed parameter sensitivity analysis, which could not have been carried out during site tests at the inverter station. Comparison of simulation results and the results of some preliminary field tests is also documented.
机译:描述了一种联合VAr(伏安电抗)控制器,该控制器设计用于Manitoba Hydro的Dorsey换流站。使用全数字实时模拟器以闭环模式对控制器进行了测试。通过执行广泛的模拟系统干扰,可以在安装控制器之前对其进行验证。事实证明,该测试对验证控制器概念,确认控制器软件的正确运行以及进行参数灵敏度分析很有用,而这在逆变器站的现场测试中是无法进行的。还记录了模拟结果与一些初步现场测试结果的比较。