首页> 外文期刊>Power Delivery, IEEE Transactions on >A Synchrophasor-Based Fault Location Method for Three-Terminal Hybrid Transmission Lines With One Off-Service Line Branch
【24h】

A Synchrophasor-Based Fault Location Method for Three-Terminal Hybrid Transmission Lines With One Off-Service Line Branch

机译:具有离线服务分支的三端混合输电线路基于同步相量的故障定位方法

获取原文
获取原文并翻译 | 示例

摘要

This letter presents a fault location technique for three-terminal hybrid AC transmission lines with one off-service line branch by using synchrophasor data obtained from buses which are connected to in-service line branches. The proposed method adopts the two-terminal fault location technique to identify the faulted line branch and locate the fault point when a fault exists on the in-service line branch. Contrarily, if a fault exists on the off-service line branch, the apparent reactance that is obtained from synchronized voltage and current phasor sets of the junction point P, and sequence networks are both chosen to calculate the exact fault point. The performance evaluation shows that the proposed idea has high accuracy under different fault types and resistance.
机译:这封信提出了一种故障定位技术,该技术用于通过使用从连接到服务中的线路分支的总线获得的同步相量数据,对具有一个服务中的线路分支的三端混合式交流输电线路进行故障定位。提出的方法采用二端故障定位技术,在运行中的支路中存在故障时,识别出故障的支路,并定位故障点。相反,如果在非服务线路分支上存在故障,则从结点P的同步电压和电流相量组以及顺序网络获得的视在电抗都将被选择来计算确切的故障点。性能评估表明,该方法在不同故障类型和电阻下具有较高的精度。