首页> 外文期刊>IEEE Transactions on Plasma Science >Axial Magnetic Field Strength Needed for a 126-kV Single-Break Vacuum Circuit Breaker During Asymmetrical Current Switching
【24h】

Axial Magnetic Field Strength Needed for a 126-kV Single-Break Vacuum Circuit Breaker During Asymmetrical Current Switching

机译:非对称电流切换过程中126 kV单断路真空断路器所需的轴向磁场强度

获取原文
获取原文并翻译 | 示例

摘要

The objective of this paper is to investigate how strong an axial magnetic field (AMF) is needed in test duty T100a for a 126-kV single-break vacuum circuit breaker (VCB) when interrupting a rated short circuit current of 40-kA rms in light of arcing contact gap, arc duration and phase shift effect. The AMF is generated by a pair of 2/3 coil-type AMF contacts. First, the accuracy of a 3-D finite element simulation of AMF is validated by an AMF measurement at a contact gap 30 mm and the error is ${<}{10%}$. After that test duty T100a of the 126-kV single-break VCB are carried out 18 times with arc duration from 3.3 to 19 ms at 40-kA rms. With a given opening displacement curve, the contact gap as arc extinguishes within a range from 12 to 50 mm corresponding to the arc duration from 3.3 to 19 ms. Then the AMF distribution of the 126-kV single-break VCB at each contact gap at which arc extinguished is simulated to analyze the current interrupting results. The results show that there are successful interruptions at the short-circuit current 40-kA rms in test duties T100a, with the shortest arcing contact gap window from 18 to 23 mm and the longest arcing contact gap of 44 mm. The shortest arcing contact gap window corresponds to the maximum AMF at the intermediate plane of the contact gap per kilo-ampere of the breaking peak current from 9.3 to 8.5 mT/kA. In addition, the longest arcing contact gap corresponds to the value of 6.1 mT/kA. The phase shift time at the center of intermediate plane of the contact gap ranged from 1.36 to 0.75 ms corresponding to an increase of arcing contact gap from 12 to 50 mm in the tests.
机译:本文的目的是研究在中断40kA rms的额定短路电流时,对于126kV单断真空断路器(VCB)的测试负荷T100a中需要多大的轴向磁场(AMF)。根据电弧接触间隙,电弧持续时间和相移效应。 AMF由一对2/3线圈型AMF触点生成。首先,通过在30 mm的接触间隙处进行AMF测量,可以验证AMF的3-D有限元模拟的准确性,并且误差为<公式公式类型=“ inline”> $ {<} {10%} $ 。之后,在40kA rms的条件下,以3.3到19 ms的电弧持续时间,对126 kV单断VCB的T100a进行了18次测试。对于给定的打开位移曲线,作为电弧的接触间隙在12至50 mm的范围内熄灭,对应于电弧持续时间3.3至19 ms。然后,模拟了每个灭弧的接触间隙处126 kV单断VCB的AMF分布,以分析当前的中断结果。结果表明,在测试任务T100a中,短路电流40 kA rms能够成功中断,电弧接触间隙窗口最短为18到23 mm,最长电弧接触间隙为44 mm。最短的电弧接触间隙窗口对应于从9.3到8.5 mT / kA的断开峰值电流每千安培的接触间隙中间平面处的最大AMF。此外,最长的电弧接触间隙对应于6.1 mT / kA的值。接触间隙中间平面中心的相移时间范围为1.36到0.75 ms,对应于测试中电弧接触间隙从12 mm增加到50 mm。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号