Reactor Switching Tests of a Vacuum Circuit Breaker, Fargo Substation Missouri River Basin Project

机译:密苏里河流域Fargo变电站真空断路器的电抗器开关试验

获取原文

摘要

A 13.8-kv vacuum-type circuit breaker at Fargo Substation performed well on reactor switching tests, usually clearing at the first current zero after contact part (for the first contact to clear). Average arcing time for the 3 phases was 0.35 cycles. This new-type breaker shows no tendency to restriking but a slight tendency to current chopping with breaker operating at 84% of continuous current rating. Moderate overvoltage transients were recorded during closing operations. The tests demonstrate a very regular pattern of clearing by the 3 interrupters during point-on-cycle switching. This breaker can be expected to provide reasonably maintenance-free reactor switching service and reasonable life within its range of applicability. Since it has low interrupting capabilities (12,000 amp, symmetrical) its use would be limited normally to locations with fault currents at or below this amount. At stations with higher interrupting current capabilities, the advantages of a vacuum breaker can be used for reactor switching service if it is applied between the reactor and the reactor neutral or by protecting the circuit with fuses of adequate interrupting capabilities. Since these tests do not provide information on interrupter life or frequency of contact adjustment, the breaker should be left in service for further study. (Author)

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号