首页> 外文期刊>Journal of power electronics >Extended Wing Technique Approach for the Detection of Winding Interturn Faults in Three-phase Transformers
【24h】

Extended Wing Technique Approach for the Detection of Winding Interturn Faults in Three-phase Transformers

机译:扩展翼技术方法检测三相变压器绕组匝间故障

获取原文
获取原文并翻译 | 示例

摘要

This paper presents a novel approach to diagnose interturn insulation faults in three-phase transformers that operate at different loading conditions. This approach is based on the loci of instantaneous symmetrical components and requires the measurement of three input primary winding currents and voltages to diagnose faults in the transformer. The effect of unbalance supply conditions, load variations, constructional imbalance, and measurement errors when this methodology is used is also investigated. Wing size or length determines the loading on the transformer. Wing travel and area determine the degree of severity of fault. Experimental results are presented for a 400/200 V, 7.5 kVA transformer to validate this method.
机译:本文提出了一种新颖的方法来诊断在不同负载条件下运行的三相变压器的匝间绝缘故障。这种方法基于瞬时对称分量的轨迹,并且需要测量三个输入初级绕组电流和电压以诊断变压器中的故障。当使用这种方法时,还研究了不平衡供应条件,负载变化,结构不平衡和测量误差的影响。翼的大小或长度决定了变压器的负载。机翼行程和区域决定了故障的严重程度。给出了针对400/200 V,7.5 kVA变压器的实验结果,以验证该方法。