Computation of current-division factors and assessment of earth-grid safety at 161/69 kV indoor-type and outdoor-type substations

机译:161/69 kV室内和室外变电站电流分流系数的计算和地网安全性评估

获取原文
获取原文并翻译 | 示例

摘要

The paper computes current-division factors and assesses earth-grid safety at 161/69 kV indoor-type and outdoor-type substations in the system of Taiwan Power Co. For computation of current-division factors, a method based on the grid current is proposed and the results obtained by the proposed method are compared with the Endrenyi method presented in IEEE 80:2000 as well as the current-distribution electromagnetic-grounding and soil-structure analysis (CDEGS) program. On the other hand, mesh and step voltages are computed and compared with minimum touch and step voltages for assessing earth-grid safety, respectively. The values of current-division factor obtained by the proposed method and the CDEGS program are smaller than those from the Endrenyi method, since coupling effects between overhead earth wires and phase conductors are taken into account. Nevertheless, the design of earthing systems at both types of 161/69 kV substations is safe for humans with 50 kg and 70 kg body weight.
机译:本文计算了台湾电力公司系统中161/69 kV室内和室外型变电站的分流系数并评估了地网安全性。为计算分流系数,一种基于电网电流的方法是将该方法与通过IEEE 80:2000提出的Endrenyi方法以及电流分布电磁接地和土壤结构分析(CDEGS)程序进行了比较。另一方面,计算网格电压和阶跃电压并将其与最小接触电压和阶跃电压进行比较,以分别评估接地网的安全性。由于考虑了架空接地线和相线之间的耦合效应,通过所提出的方法和CDEGS程序获得的分流系数的值要比从Endrenyi方法获得的值小。尽管如此,两种161/69 kV变电站的接地系统设计对于体重分别为50公斤和70公斤的人是安全的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号