Stable operation of grid-connected converters with the LCL filter is essential. Variations of the grid impedance and consequently, variations of the resonance frequency, can push the system toward instability. Also, delay that comes from sampling and PWM, could worsen the stability condition. Thus, the control system should be designed by considering these non-ideal factors. To fill in this gap, this brief presents an effective but simple method based on biquad filter, which enhances the system robustness and guarantees the system stability in a varying grid impedance condition. Besides, the suggested technique is free from employing any active damping mechanism, which in turn, increases the reliability and reduces the cost. Finally, experimental results are provided to show the accuracy of the analysis and verify the proposed method.
机译:具有LCL过滤器的网格连接转换器的稳定运行至关重要。电网阻抗的变化以及谐振频率的变化可以推动系统朝向不稳定性。此外,来自采样和PWM的延迟可能会恶化稳定条件。因此,应通过考虑这些非理想因素来设计控制系统。为了填补这一差距,本简要介绍了基于各种方面滤波器的有效但简单的方法,增强了系统的鲁棒性,并保证了不同的电网阻抗条件下的系统稳定性。此外,建议的技术不采用任何有源阻尼机构,反过来增加可靠性并降低成本。最后,提供了实验结果以显示分析的准确性并验证所提出的方法。