Improvement in airflow and temperature distribution with an in-rack UFAD system at a high-density data center

机译:在高密度数据中心的机架UFAD系统中的气流和温度分布的改进

获取原文
获取原文并翻译 | 示例

摘要

This paper introduced and analyzed a new concept where an under-floor air supply (UFAD) system with cold aisle containment (CAC) is replaced by a new in-rack UFAD system called an in-rack cold aisle (IR-CA). The IRCA system is analyzed using CFD simulation, and on-site measurement was carried out to validate the feasibility and reliability of simulation models. The study is divided into eight cases with seven different dimensions for the rack air inlet (2.2 m. 0.6 m, 0.2 m. 0.6 m, 0.3 m. 0.6 m, 0.4 m. 0.6 m, 0.5 m. 0.6 m, 0.6 m. 0.6 m, and 0.7 m. 0.6 m), while an additional partition plane is placed in Case 8 with a 0.6 m. 0.6-m in-rack air inlet. The thermal distribution is compared and analyzed in the eight cases, while cooling efficiency and energy saving is compared between the original and optimal cases. The results showed that the optimal thermal distribution is achieved in Case 8 with a 0.6 m. 0.6 m IR-CA and partition plane, while the thermal distribution in Case 8 with SAT of 23. C is still much better than that in the original DC. The application of a 0.6 m. 0.6 m IR-CA and partition plane can save approximately 98 kW h/day in electricity consumption in the studied DC. A new evaluation index named the MS index is proposed to evaluate the optimization effects of the optimization model based on the original model.
机译:本文介绍并分析了一种新的概念,其中具有冷过通道容纳(CAC)的地板楼层空气供应(UFAD)系统被称为机架内冷通道(IR-CA)的新型架构UFAD系统代替。使用CFD仿真分析IRCA系统,并进行现场测量以验证仿真模型的可行性和可靠性。该研究分为8例,齿条空气入口七种不同尺寸(2.2米,0.2米0.6米,0.3米0.6米,0.4米0.6米,0.5米。0.6米,0.6米。 0.6米和0.7米。0.6米),而另外的分隔壁放置在具有0.6米的情况8中。 0.6米的机架式空气入口。在八种情况下比较和分析了热分布,而在原始和最佳情况下比较了冷却效率和节能。结果表明,在0.6米的情况下实现最佳的热分布。 0.6米IR-CA和隔板,而带有SAT 23的情况下的热分布仍然比原始DC中的更好。施用0.6米。 0.6米IR-CA和隔板可以在研究的DC中节省大约98 kW H /天的电力消耗。提出了一种名为MS索引的新评估索引,以评估基于原始模型的优化模型的优化效果。

著录项

  • 来源
    《Building and Environment》 |2020年第1期|106495.1-106495.14|共14页
  • 作者单位

    Tongji Univ Sch Mech Engn 4800 Caoan Rd Shanghai 201804 Peoples R China|Aalto Univ Sch Engn POB 14400 FI-00076 Espoo Finland;

    Nanjing Tech Univ Coll Urban Construct POB 76 Nanjing 210009 Peoples R China;

    Nanjing Tech Univ Coll Urban Construct POB 76 Nanjing 210009 Peoples R China;

    Tongji Univ Sch Mech Engn 4800 Caoan Rd Shanghai 201804 Peoples R China;

    Nanjing Tech Univ Coll Urban Construct POB 76 Nanjing 210009 Peoples R China|Aalto Univ Sch Engn POB 14400 FI-00076 Espoo Finland;

    Nanjing Yangtze River Urban Architectural Design Nanjing 210002 Peoples R China;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Data centers; Airflow management; In-rack UFAD; Temperature distribution; Velocity distribution; Energy saving;

    机译:数据中心;气流管理;机架UFAD;温度分布;速度分布;节能;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号