首页> 外文期刊>IEEE Transactions on Applied Superconductivity >Design of an HTS Fault Current Limiting Module for an MVDC Power Grid
【24h】

Design of an HTS Fault Current Limiting Module for an MVDC Power Grid

机译:用于MVDC电网的HTS故障电流限制模块的设计

获取原文
获取原文并翻译 | 示例

摘要

We have studied a DC circuit breaker with an HTS fault current limiting (FCL) module for MVDC(Medium-Voltage Direct Current) power grid. The attached FCL module can reduce the burden of the circuit breaker to make the system break the fault current faster as well as safer. In this paper, we will present the design of an HTS fault current limiting module with 2G REBCO conductor for the MVDC power grid with the rated voltage of 15 & x00A0;kV. Among several different type of 2G REBCO conductor from different suppliers, we selected the most suitable conductor, which was SuNAM & x0027;s stabilizer free REBCO conductor, based on the overcurrent test results. And we performed the circuit simulation to verify the module & x0027;s validity for rated current of 3 kA in 15 kV class DC grid.
机译:我们研究了具有HTS故障电流限制(FCL)模块的直流断路器,用于MVDC(中压直流电)电网。附加的FCL模块可以减少断路器的负担,使系统打破故障电流并更快,更安全。在本文中,我们将向MVDC电网具有2G Rebco导体的HTS故障电流限制模块的设计,额定电压为15&x00a0; kV。在来自不同供应商的几种不同类型的2G Rebco导体中,我们选择了最合适的导体,这是Sunam&X0027; S稳定器免费Rebco指挥,基于过流测试结果。我们执行了电路仿真,以验证模块和X0027;在15 kV类直流电网中为3 ka的额定电流的有效性。