首页> 外文会议>International Conference on Energy and Environmental Protection >Differences of SF6 Byproducts in Simulated Electric Equipment of Overheating Faults in Different Condition
【24h】

Differences of SF6 Byproducts in Simulated Electric Equipment of Overheating Faults in Different Condition

机译:不同条件下过热故障模拟电气设备SF6副产品的差异

获取原文

摘要

The decomposition of sulfur hexafluoride (SF6) in overheated electric equipment at different temperature and humidity was simulated in the study. SF6 is significantly decomposed at 350°C. SF6 is more easily decomposed in high humidity than in low humidity. The concentrations of SF6 byproducts, such as sulfur dioxide (S02), sulfureted hydrogen (H2S) and hydrofluoric acid (HF), in high humidity are much higher than those in low humidity. Moisture in electric equipment accelerates the decomposition of SF6. In order to insure the safety operation of electric equipment, moisture in the equipment should be strictly controlled. SF6 will be decomposed to format HF. The concentration of HF will decrease when its concentration increases up to a certain concentration. It may be because that HF was strongly corrosive and its corrosion to inner equipment made the concentration of HF decreasing.
机译:在研究中,模拟了在不同温度和湿度下过热电气设备中的六氟化锂(SF6)的分解。 SF6在350°C下显着分解。 SF6更容易在高湿度下分解而不是低湿度。高湿度的SF6副产物(例如二氧化硫(SO 2),硫酸氢(H 2 S)和氢氟酸(HF)的浓度远高于低湿度。电气设备中的水分加速了SF6的分解。为了确保电气设备的安全运行,应严格控制设备中的水分。 SF6将分解为格式化HF。当其浓度增加到一定浓度时,HF的浓度将降低。它可能是因为HF强烈腐蚀性,并且对内部设备的腐蚀使得HF减小的浓度。