摘要

Through the long time track examination and disintegration to SF6 circuit breaker, we obtain the massive monitor data and massive pictures. The criteria of resuming insulation discharge failure conforming to CSO2/CH2S>7, is quite broad to SO2 and the H2S concentration permission. Even if it reaches 100μL/L, it will not be in danger immediately to the safe operation of equipment. We may plan, arrange, and overhaul calmly. When obtaining the bare conductor overheating failure, it has not involved the resuming insulation. We may use the resuming insulation discharge failure criterion.
机译:通过长时间的跟踪检查和对SF6断路器的分解,我们获得了大量的监控数据和大量的图片。恢复符合CSO2 / CH2S> 7的绝缘放电故障的标准,对于SO2和H2S浓度许可是相当宽泛的。即使达到100μL/ L,也不会立即对设备的安全运行造成危险。我们可能会冷静地计划,安排和大修。当获得裸导体过热故障时,它不涉及恢复绝缘。我们可以使用恢复绝缘放电失败准则。