首页> 外文会议>Conference Record of the IEEE Industry Applications >Evaluation of Cascade-Multilevel Converter based STATCOM for Arc Furnace Flicker Mitigation
【24h】

Evaluation of Cascade-Multilevel Converter based STATCOM for Arc Furnace Flicker Mitigation

机译:基于CASCADE-MULTILEVEL转换器的弧形炉闪烁缓解评估

获取原文

摘要

As an industry customer of electric power, Electrical Arc Furnace (EAF) is a major flicker source that causes major power quality problem. For a 40 MVA EAF at Tennessee, USA, a Cascade-Multilevel Converter (CMC) based STATCOM with high bandwidth is proposed for EAF flicker mitigation. In this paper, flicker mitigation techniques by using a CMC-based STATCOM are presented and verified through a Transient Network Analyzer (TNA) system. The required STATCOM capacity is first studied through a generalized steady-state analysis. Secondly, the STATCOM control strategy for flicker mitigation is introduced and simulation results are given. Finally, a TNA system of the STATCOM and EAF system are designed and implemented. Experimental results from the TNA test show that the proposed CMC-based STATCOM and its controller can efficiently and rapidly mitigate the EAF flicker.
机译:作为电力的行业客户,电弧炉(EAF)是一个主要的闪烁源,导致主要的电能质量问题。对于美国田纳西州的40 MVA EAF,提出了一种基于Cascade - 多级转换器(CMC)的STATCOM,具有高带宽的STATWID,用于EAF闪烁缓解。在本文中,通过使用基于CMC的Statcom进行闪烁缓解技术,并通过瞬态网络分析器(TNA)系统验证。首先通过广义稳态分析研究所需的Statcom容量。其次,引入了闪烁缓解的Statcom控制策略,并给出了仿真结果。最后,设计并实施了Statcom和EAF系统的TNA系统。 TNA测试的实验结果表明,所提出的基于CMC的Statcom及其控制器可以有效地迅速减轻EAF闪烁。