As an industry customer of electric power, an electrical arc furnace (EAF) is a major flicker source that causes major power quality problems. For a 40-MVA EAF in Tennessee, USA, a cascade-multilevel converter (CMC)-based STATic synchronous COMpensator (STATCOM) with high bandwidth is proposed for EAF flicker mitigation. In this paper, flicker mitigation techniques by using a CMC-based STATCOM are presented and verified through a transient network analyzer (TNA) system. The required STATCOM capacity is first studied through a generalized steady-state analysis. Second, the STATCOM control strategy for flicker mitigation is introduced, and simulation results are given. Finally, a TNA system of the STATCOM and an EAF system are designed and implemented. Experimental results from the TNA test show that the proposed CMC-based STATCOM and its controller can efficiently and rapidly mitigate the EAF flicker
机译:作为电力行业的客户,电弧炉(EAF)是导致重大电能质量问题的主要闪烁源。对于美国田纳西州的40 MVA EAF,提出了一种基于级联多电平转换器(CMC)的高带宽静态同步补偿器(STATCOM),用于缓解EAF闪烁。本文提出并使用了基于CMC的STATCOM来减轻闪烁,并通过瞬态网络分析仪(TNA)系统进行了验证。首先通过广义稳态分析来研究所需的STATCOM能力。其次,介绍了用于减轻闪烁的STATCOM控制策略,并给出了仿真结果。最后,设计并实现了STATCOM的TNA系统和EAF系统。 TNA测试的实验结果表明,所提出的基于CMC的STATCOM及其控制器可以有效且快速地缓解EAF闪烁