首页> 外文会议>IEEE International Conference on Solid Dielectrics >Degradation of Mica in Stator Insulation in Service 23 Years for A Large Generator
【24h】

Degradation of Mica in Stator Insulation in Service 23 Years for A Large Generator

机译:大型发电机服务23年中定子绝缘中云母的降解

获取原文
获取外文期刊封面目录资料

摘要

Degradation behavior of mica in stator insulation under operating stresses was invested through chemical formula analysis of crystal based on X-ray diffraction method. The insulation specimens were cut from a standby and an aged stator bar in operation for 23 years in a 300MW/18kV generator. Complicate changes were found on all mica crystal in aged insulation. Firstly, atom count of potassium in mica crystal decreases to 0.75 from 1. Secondly, the aluminum ion in mica crystal of aged insulation is replaced with ferrum and lithium ions, and the hydroxyl (OH) is with fluorine. Lastly, there is a trend of crystal lattice parameters increasing. Degradation mechanism corresponding to the degradation behavior of mica was discussed.
机译:基于X射线衍射法的晶体分析,研究了在操作应力下的定子绝缘中的云母在定子绝缘中的降解行为。在300MW / 18KV发生器中,从备用待机和老化定子杆切割绝缘样品23岁。在老化绝缘中的所有云母晶体上发现了复杂的变化。首先,云母晶体的钾的原子计数从1.第二,用铁霉和锂离子的云母晶体中的铝离子,羟基(OH)用氟代替。最后,晶格参数增加了趋势。讨论了对应于云母的降解行为的降解机制。