首页> 外文会议>Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society >Separable insulated connector loadbreak testing. II. Providingreliability assurances
【24h】

Separable insulated connector loadbreak testing. II. Providingreliability assurances

机译:可分离的绝缘连接器负载破坏测试。二。提供可靠性保证

获取原文

摘要

For pt.I see ibid., p.67-72 (1991). A statistical analysis of theANSI/IEEE loadbreak switching test shows that it cannot offer utilitiesreliability assurances. An alternative approach to loadbreak testing ispresented. It utilizes the concepts of a generic switching reliabilitycharacteristic, composite system switching reliability (CSSR), and lowerconfidence limits to relate laboratory test performance to utilityreliability needs. The major focus is the number of samples, which mustbe tested in the laboratory, needed to determine in-service reliabilityto some specified confidence level
机译:关于pt,我参见同上,第67-72页(1991)。的统计分析 ANSI / IEEE负载中断切换测试表明它无法提供实用程序 可靠性保证。负载破坏测试的另一种方法是 提出了。它利用了通用开关可靠性的概念 特性,复合系统切换可靠性(CSSR)及更低 将实验室测试性能与公用事业联系起来的置信度限制 可靠性需求。主要重点是样本数量,必须 在实验室中进行测试,以确定使用中的可靠性 达到指定的置信度

著录项