首页> 外文会议>ASME Power Conference >EXPERIMENTAL INVESTIGATION OF PERFORMANCE EFFECT OF WORKING PARAMETERS ON BI-EVAPORATOR COMPRESSION/EJECTION REFRIGERATION SYSTEM
【24h】

EXPERIMENTAL INVESTIGATION OF PERFORMANCE EFFECT OF WORKING PARAMETERS ON BI-EVAPORATOR COMPRESSION/EJECTION REFRIGERATION SYSTEM

机译:双蒸发器压缩/喷射制冷系统工作参数性能效应的实验研究

获取原文

摘要

In this paper, a bi-evaporator compression/ejection refrigeration is experimental investigated to recycle the throttling loss in traditional vapor compression refrigeration cycle by using an ejector. The effects of working parameters on the system performance are mainly analyzed. The results are as follows: the ejector entrainment ratio decreases as the condenser and the high-temperature inlet water temperature increases, but rises with the increasing of low-temperature evaporator inlet water temperature; the system COP rises with the decreasing of inlet water temperature of condenser, and increases with the rise of inlet water temperature of high-temperature evaporator; the inlet water temperature of the condenser and the high-temperature has greater influences on the performance of BCERC system. The system COP increases about 0.25 when the condenser inlet water temperature decreases per 5°C; while the system COP rise about 0.114 as the high-temperature evaporator inlet water temperature increases per 5°C. The low-temperature evaporator inlet water temperature has little effects on the performance of the BCERC system. The results can be references for the design and operation of the BCERC system.
机译:在本文中,实验研究了双蒸发器压缩/喷射制冷,以通过使用喷射器来回收传统蒸汽压缩制冷循环中的节流损失。主要分析了工作参数对系统性能的影响。结果如下:喷射器夹带比随着冷凝器和高温入口水温度的增加而降低,但随着低温蒸发器入口水温度的增加而上升;系统警察随着冷凝器的入口水温的降低而上升,随着高温蒸发器的入口水温的升高而增加;冷凝器的入口水温和高温对BCERC系统的性能产生了更大的影响。当冷凝器入口水温降低每5°C时,系统警察增加约0.25;当系统警察增加约0.114时,随着高温蒸发器入口水温度的增加,每5℃增加。低温蒸发器入口水温对BCERC系统的性能几乎没有影响。结果可以是BCERC系统的设计和操作的参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号