首页> 外文期刊>International journal of air-conditioning and refrigeration >Experimental Investigation of Performance Enhancement of a Vapor Compression Refrigeration System by Vortex Tube Cooling
【24h】

Experimental Investigation of Performance Enhancement of a Vapor Compression Refrigeration System by Vortex Tube Cooling

机译:涡旋管冷却蒸汽压缩制冷系统性能提高的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

This study aimed to analyze the difference in operation of the vapor compression refrigeration (VCR) system with vortex tube cooling. By using varied loads, experiments were conducted on the evaporator section of a vapor compression refrigeration system. In an attempt to improve the use of subcooling for the refrigeration, the effect of subcooling of refrigerant by vortex tube cooling was likewise examined. The test conditions included various loads (25%, 50%, 75% and 100%) and cold mass fractions (25%, 50% and 75%). This research described coefficient of performance (COP) as one of the significant parameters, in addition to heat rejection and refrigerating effect. The ideal efficiency appeared to be with the cold mass fraction of 25% and load of 100%, as identified by the results. Consequently, the COP could be enhanced by 5.16% along with an approximately 4.36% decline in average power use. Improved guidelines for vapor compression refrigeration systems to enhance the operation of the system are an expected benefit of this study.
机译:本研究旨在分析涡旋管冷却蒸汽压缩制冷(VCR)系统的运行差异。通过使用各种载荷,在蒸汽压缩制冷系统的蒸发器部分上进行实验。为了改善使用过冷却的制冷,通过涡旋管冷却使制冷剂过冷却的作用同样检查。试验条件包括各种载荷(25%,50%,75%和100%)和冷质量级分(25%,50%和75%)。该研究将性能系数(COP)作为重要参数之一,除了进行排出和冷冻效果之外。如结果所鉴定的,理想的效率似乎具有25%的25%和100%的载荷。因此,COP可以增强5.16%,并且平均电力使用下降约4.36%。改进的蒸汽压缩制冷系统指南,以提高系统的运行是本研究的预期益处。

著录项

  • 来源
    《International journal of air-conditioning and refrigeration》 |2020年第2期|2050018.1-2050018.10|共10页
  • 作者单位

    Rattanakosin College for Sustainable Energy and Environment Rajamangala University of Technology Rattanakosin Phutthamonthon Nakhon Pathom 73170 Thailand;

    Rattanakosin College for Sustainable Energy and Environment Rajamangala University of Technology Rattanakosin Phutthamonthon Nakhon Pathom 73170 Thailand;

    Center of Excellence in Electromagnetic Energy Utilization in Engineering (CEEE) Department of Mechanical Engineering Faculty of Engineering Thammasat University (Rangsit Campus ) Klong Luang Pathumthani 12120 Thailand;

    Rattanakosin College for Sustainable Energy and Environment Rajamangala University of Technology Rattanakosin Phutthamonthon Nakhon Pathom 73170 Thailand;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Coefficient of performance; subcooling; vortex tube;

    机译:性能系数;过冷;涡旋管;