首页> 外文会议>ASME InterPack conference;IPACK2009 >REFRIGERATION HEAT EXCHANGER SYSTEMS FOR SERVER RACK COOLING IN DATA CENTERS
【24h】

REFRIGERATION HEAT EXCHANGER SYSTEMS FOR SERVER RACK COOLING IN DATA CENTERS

机译:数据中心服务器机架冷却的制冷换热系统

获取原文

摘要

In 2005, IBM released a water cooled heat exchanger product that significantly enhanced data center cooling capability while also demonstrating substantial energy savings. In 2008, IBM released an enhanced water less solution to cool the electronic racks via a R410A refrigerant based vapor compression system, which is the focus of this paper. The paper provides a detailed description of device and coolant loop construction, the experimental thermal data collected, as well as a discussion of its' cooling energy efficiency relative to both typical air cooled facilities and water cooled heat exchangers, respectively. A data center level case study was performed with experimental measurements collected and discussed herein. Significant energy savings were realized even when the heat exchanger devices were implemented on a small part of the data center. Based on the test data and the experimental data center study, the CRAC units based loops have a COP of 1.95, while the refrigerant refrigerant heat exchanger loop has a COP of 5.0.
机译:2005年,IBM发布了一种水冷式热交换器产品,该产品显着增强了数据中心的冷却能力,同时还显示出了可观的节能效果。 2008年,IBM发布了一种增强型的无水解决方案,通过基于R410A制冷剂的蒸汽压缩系统来冷却电子机架,这是本文的重点。本文详细描述了设备和冷却剂回路的结构,收集了实验热数据,并讨论了其相对于典型的风冷设备和水冷热交换器的冷却能效。使用本文收集和讨论的实验测量结果进行了数据中心级别的案例研究。即使将热交换器设备安装在数据中心的一小部分上,也可以实现显着的节能效果。根据测试数据和实验数据中心研究,基于CRAC单元的回路的COP为1.95,而制冷剂-制冷剂热交换器的回路的COP为5.0。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号