首页> 外文期刊>Energy and Buildings >Research of an integrated cooling system consisted of compression refrigeration and pump-driven heat pipe for data centers
【24h】

Research of an integrated cooling system consisted of compression refrigeration and pump-driven heat pipe for data centers

机译:由压缩制冷和泵驱动热管组成的数据中心集成冷却系统的研究

获取原文
获取原文并翻译 | 示例
           

摘要

An integrated cooling system is developed for the environmental control of all-year-round running data centers with high heat load. The system is consisted of a vapor compression refrigeration unit connected with a separated heat pipe unit by an evaporative condenser. Based on the outdoor temperature, the system can operate on three modes: vapor compression mode, dual refrigeration mode and heat pipe mode. The cooling capacity of vapor compression unit is regulated via volume control of six paralleled scroll compressors, while that of heat pipe unit is adjusted by frequency conversion outdoor fan. The experimental results indicate that the cooling capacity of the system has a nearly constant value of 200 kW, and EER changes from 21.2 to 3.1 when the outdoor temperature increases from -5 degrees C to 45 degrees C. The theoretical calculation and analysis show that, compared with air cooling direct expansion unit and air cooling dual source chiller, the proposed system has the lowest annual energy consumption with highest energy efficiency. So it can be the preferred choice for all-year-round running data centers especially in regions with low average annual temperature. (C) 2019 Elsevier B.V. All rights reserved.
机译:开发了一个集成的冷却系统,用于对具有高热负荷的全年运行的数据中心进行环境控制。该系统由蒸汽压缩制冷单元组成,该蒸汽压缩制冷单元通过蒸发冷凝器与独立的热管单元相连。根据室外温度,系统可以在三种模式下运行:蒸汽压缩模式,双重制冷模式和热管模式。蒸汽压缩单元的冷却能力通过六个并联涡旋压缩机的音量控制来调节,而热管单元的冷却能力则通过变频室外风扇进行调节。实验结果表明,当室外温度从-5摄氏度增加到45摄氏度时,系统的制冷量几乎恒定为200 kW,EER从21.2变为3.1。理论计算和分析表明,与风冷直接膨胀机组和风冷双源冷水机相比,该系统的年度能耗最低,能效最高。因此,它可能是全年运行的数据中心的首选,尤其是在年平均温度较低的地区。 (C)2019 Elsevier B.V.保留所有权利。

著录项

  • 来源
    《Energy and Buildings》 |2019年第3期|16-23|共8页
  • 作者单位

    Hefei Univ Technol, Sch Automot & Transportat Engn, Hefei, Anhui, Peoples R China;

    Hefei Univ Technol, Sch Automot & Transportat Engn, Hefei, Anhui, Peoples R China;

    Hefei Univ Technol, Sch Automot & Transportat Engn, Hefei, Anhui, Peoples R China;

    Hefei Univ Technol, Sch Automot & Transportat Engn, Hefei, Anhui, Peoples R China;

    Yangzi Air Conditioner Co Ltd, Chuzhou, Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Integrated system; Heat pipe; Natural cooling; Dual mode; Data center;

    机译:集成系统;热管;自然冷却;双模式;数据中心;