U cosϕ out-of-step criterion was studied in this paper. It is found that U cosϕ criterion can only partially capture the variation of the oscillation center voltage, so a method using PMU devices to measure both ends of the bus voltage phase angle difference as a secondary criterion combined with U cosϕ criterion is proposed to locate of step oscillation center accurately. equivalent two-machine system model is established to verify the out-of-step based on both ends of the bus voltage phase angle difference by PSCAD simulation tools. The results show that the method can take advantage of the multiport measurement to recognize the out-of-step system state timely so that the contact line can be break reasonably and quickly.
机译:U cosϕ 本文研究了阶梯标准。 发现你cosϕ 标准只能部分地捕获振荡中心电压的变化,因此使用PMU器件的方法测量总线电压相位角差的两端,作为辅助标准与U COS&#x03d5组合; 建议准确地定位步进振荡中心的标准。 建立了等效的双机系统模型,以基于PSCAD仿真工具的总线电压相位角差的两端验证超步。 结果表明,该方法可以利用多端口测量来及时识别超步系统状态,使得接触线可以合理且快速地打破。