Study on improved out-of-step splitting criterion based on the PMU

机译:基于PMU的改进失步分裂准则研究

获取原文

摘要

U cosϕ; out-of-step criterion was studied in this paper. It is found that U cosϕ; criterion can only partially capture the variation of the oscillation center voltage, so a method using PMU devices to measure both ends of the bus voltage phase angle difference as a secondary criterion combined with U cosϕ; criterion is proposed to locate of step oscillation center accurately. equivalent two-machine system model is established to verify the out-of-step based on both ends of the bus voltage phase angle difference by PSCAD simulation tools. The results show that the method can take advantage of the multiport measurement to recognize the out-of-step system state timely so that the contact line can be break reasonably and quickly.
机译:U cosϕ;本文研究了失调准则。发现U cosϕ;准则仅能部分捕获振荡中心电压的变化,因此,使用PMU装置测量母线电压两端相位差的方法是结合U cosϕ作为次级准则。提出了精确定位步进振动中心的准则。建立等效的两机系统模型,以通过PSCAD仿真工具基于母线两端电压相角差来验证失步。结果表明,该方法可以利用多端口测量技术及时识别失步的系统状态,从而可以合理,快速地断开接触线。