首页> 外文会议>International symposium on heating, ventilating and air conditioning >HEAT AND MOISTURE TRANSFER CHARACTERISTICS OF A PLATE-TYPE ENTHALPY EXCHANGER MADE OF PAPER
【24h】

HEAT AND MOISTURE TRANSFER CHARACTERISTICS OF A PLATE-TYPE ENTHALPY EXCHANGER MADE OF PAPER

机译:用纸张制成的板式焓交换器的热量和湿度传递特性

获取原文

摘要

In this study, heat and moisture transfer data of an enthalpy exchanger were obtained varying the indoor and outdoor condition systematically. At the same time, equilibrium water content ratios of the membrane were measured. It is shown that equilibrium water content ratio of the membrane increases with the increase of relative humidity. The effect of temperature on equilibrium water content ratio, however, is rather complex. It decreases with the increase of temperature to a certain value, and then increases with further increase of temperature. Moisture transfer effectiveness of the enthalpy exchanger is also affected by relative humidity and temperature. Heat transfer effectiveness, however, is independent of relative humidity and temperature. Moisture transfer effectiveness of the enthalpy exchanger was successfully correlated by equilibrium water content ratio of the membrane.
机译:在本研究中,系统地获得了焓交换器的热量和湿气转移数据,并系统地改变室内和室外条件。同时,测量膜的平衡水含量比。结果表明,膜的平衡水含量比随着相对湿度的增加而增加。然而,温度对平衡水含量比的影响是相当复杂的。随着温度的增加降低到一定值,然后随着温度的进一步增加而增加。焓交换器的湿度转移效果也受相对湿度和温度的影响。然而,传热效果与相对湿度和温度无关。焓交换器的湿度转移效果通过膜的平衡水含量比成功地相关。