首页> 外文会议>IEEE Industry Applications Society Annual Meeting >Location the Origin of Feeder Level Harmonics Utilizing Remote THD Measurements
【24h】

Location the Origin of Feeder Level Harmonics Utilizing Remote THD Measurements

机译:位置利用远程THD测量的馈线级谐波的起源

获取原文

摘要

The drive for power delivery efficiency has led to many utility companies installing Voltage and VAr Optimization applications, which rely upon capacitor banks installed throughout a feeder to regulate voltage and substation VArs. Due to heating effects, harmonic currents that are injected by customers can inhibit the operational effectiveness of such applications. This paper describes a method for indentifying the originating locations of feeder level harmonics with the use of THD measurements retrieved remotely from capacitor banks and a single harmonic spectrum analysis. The authors utilize a simplified distribution system model to perform current injection calculations to match the measured feeder level distortion that is identified from remote monitoring. The spectrum analysis measurement is utilized to determine the individual harmonics of the THD measurements and to develop harmonic source parallel impedances. The process was applied to an existing Volt/VAr application that was frequently experiencing 9% voltage THD.
机译:用于电力输送效率的驱动器导致许多公用事业公司安装电压和VAR优化应用,该公司依靠整个馈线安装的电容器组来调节电压和变电站变电站。由于加热效果,由客户注入的谐波电流可以抑制这些应用的操作效率。本文介绍了一种用于识别进料器电平谐波的始发位置的方法,通过使用电容器组远程检索的THD测量和单次谐波频谱分析。作者利用简化的分配系统模型来执行当前的注射计算,以匹配从远程监控中识别的测量馈线级失真。光谱分析测量用于确定THD测量的各个谐波,并开发谐波源并行阻抗。该过程应用于经常遇到9%电压THD的现有Volt / VAR应用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号