首页> 外文会议>2011 IEEE Industry Applications Society Annual Meeting >Location the origin of feeder level harmonics utilizing remote THD measurements
【24h】

Location the origin of feeder level harmonics utilizing remote THD measurements

机译:利用远程THD测量来定位馈线电平谐波的起源

获取原文

摘要

The drive for power delivery efficiency has led to many utility companies installing Voltage and VAr Optimization applications, which rely upon capacitor banks installed throughout a feeder to regulate voltage and substation VArs. Due to heating effects, harmonic currents that are injected by customers can inhibit the operational effectiveness of such applications. This paper describes a method for indentifying the originating locations of feeder level harmonics with the use of THD measurements retrieved remotely from capacitor banks and a single harmonic spectrum analysis. The authors utilize a simplified distribution system model to perform current injection calculations to match the measured feeder level distortion that is identified from remote monitoring. The spectrum analysis measurement is utilized to determine the individual harmonics of the THD measurements and to develop harmonic source parallel impedances. The process was applied to an existing Volt/VAr application that was frequently experiencing 9% voltage THD.
机译:供电效率的提高导致许多公用事业公司安装了电压和VAr优化应用程序,这些应用程序依赖于整个馈线中安装的电容器组来调节电压和变电站VArs。由于发热的影响,客户注入的谐波电流会抑制此类应用的运行效率。本文介绍了一种通过从电容器组远程获取的THD测量值和单次谐波频谱分析来确定馈线电平谐波的始发位置的方法。作者利用简化的配电系统模型来执行电流注入计算,以匹配从远程监控中识别出的测得的馈线水平失真。频谱分析测量用于确定THD测量的各个谐波,并产生谐波源并联阻抗。该过程被应用于经常经历9%电压THD的现有Volt / VAr应用。