首页> 外文会议>International congress on exposition noise control engineering >Applying an active noise barrier on a 110 KV power transformer in Hunan
【24h】

Applying an active noise barrier on a 110 KV power transformer in Hunan

机译:在湖南110 kV电力变压器上应用有源噪声屏障

获取原文

摘要

There are increasing needs to reduce the transformer noise recently in China because some residential buildings developed recently are located more and more close to the pre-existing substations. Passive barriers are often used around the outdoor transformers to block the noise. However, the noise reduction performance of the barriers is poor in low frequency range, especially when the noise wavelength is larger than the height of the barrier. Consequently, active noise control (ANC) system has been investigated to enhance the insertion loss of traditional barrier in low frequency. In this paper, a prototype active noise barrier (ANB) was developed and applied to a practical case. Physical system of the ANB was designed in first. Then a decentralized feedforward ANC system composed of the cascaded active units was developed, and the waterproof structures were developed to protect the elements of the system. Again, experiments were carried out on the rooftop of a five-floor building to verify the effectiveness of the system. Finally, the practical application in Hunan is investigated, in which the noise reduction of the 110kV power transformers was needed.
机译:最近,在中国,降低变压器噪声的需求日益增加,因为最近开发的一些住宅建筑越来越靠近现有的变电站。通常在室外变压器周围使用无源屏障来阻挡噪声。然而,在低频范围内,尤其是当噪声波长大于屏障的高度时,屏障的降噪性能很差。因此,已经对有源噪声控制(ANC)系统进行了研究,以增强传统屏障在低频下的插入损耗。在本文中,原型有源噪声屏障(ANB)被开发并应用于实际案例。首先设计了ANB的物理系统。然后,开发了由级联有源单元组成的分散式前馈ANC系统,并开发了防水结构来保护系统的元件。同样,在五层楼房的屋顶上进行了实验,以验证该系统的有效性。最后,对湖南的实际应用进行了研究,其中需要降低110kV电力变压器的噪声。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号