The electromagnetic processes that occur when opening and closing a high-voltage circuit-breaker at the beginning of a power line with an unloaded transformer are investigated. At the instants when a power line is switched on and off, it may happen that all its phases are not opened and closed simultaneously. There may be situations when two phases are opened and one phase is closed, and when two phases are closed and one phase is opened. The overvoltages that occur under these conditions are called ferroresonance overvoltages. The incomplete-phase conditions are analysed taking the skin-effect and the corona into account. The results obtained enable a protective device to be selected and the effect due to the current through an overvoltage limiter to be evaluated.
机译:研究了在变压器空载的情况下在电力线的开头断开和闭合高压断路器时发生的电磁过程。在接通和断开电源线的瞬间,可能会发生其所有相位未同时打开和关闭的情况。可能存在两相断开而一相闭合,两相闭合而一相断开的情况。在这些条件下发生的过电压称为铁磁谐振过电压。考虑到集肤效应和电晕,分析了不完全相条件。获得的结果使得能够选择保护装置,并且能够评估由于通过过压限制器的电流引起的影响。